ANALISA KINERJA ARRESTER TERHADAP FLASHOVER PADA SALURAN TRANSMISI 150 KV DI PT. PLN UPT PADANG
| dc.contributor.advisor | Novizon, Novizon | |
| dc.contributor.author | Nadia, Anggrahini | |
| dc.date.accessioned | 2026-09-24T21:14:07Z | |
| dc.date.issued | 2021-02-16 | |
| dc.description | Novizon, Ph.D | |
| dc.description.abstract | Petir merupakan fenomena alam yang disebabkan oleh adanya pelepasan muatan dari awan yang bermuatan ke bumi. Petir terjadi dalam waktu yang sangat singkat dan dapat menyebabkan kerusakan serius pada sistim tenaga. Petir merupakan salah satu penyebab utama gangguan listrik di saluran transmisi, seperti kegagalan pada isolator yang menyebabkan flashover. Penelitian ini, mensimulasikan dan menganalisa efek petir dan parameternya terhadap flashover serta upaya dalam mengatasi dampak sambaran petir terhadap saluran transmisi. Metoda dan analisa yang digunakan yaitu dengan mensimulasikan dan menganalisa pengaruh parameter petir berupa kecuraman dan amplitudo terhadap flashover. Simulasi pada penelitian ini menggunakan software Alternative Transients Program (ATP) dengan memodelkan sambaran petir dan semua komponen saluran transmisi serta arrester. Hasil yang diperoleh adalah karakteristik petir 1,2/50 us dan 8/20 us dengan amplitude petir 13 kA menghasilkan tegangan lebih besar yaitu 967 kV dan 720 kV yang dapat menyebabkan terjadi flashover. Amplitudo petir sebesar 10 kA dengan karakeristik 1,2/50 us kenaikan tegangan lebih tidak menyebabkan terjadinya flashover. Flashover pada phasa A mulai terjadi pada amplitudo sebesar 20 kA dan flashover pada phasa A dan B terjadi pada amplitudo 30 kA. Pada amplitudo 40 kA atau lebih maka flashover terjadi pada semua phasa. Dari tiga jenis tanah yang digunakan pada simulasi ini, maka jenis tanah liat dengan tahanan pentanahan sebesar 33,51 ohm tidak berpengaruh terhadap flashover untuk arus petir sebesar 10 kA, sedangkan jenis tanah berpasir dan tanah berbatu flashover terjadi masing-masing pada phasa A. Petir sebesar 20 kA menyebabkan flashover pada phasa A untuk jenis tanah liat. Dan untuk tanah berpasir dan berbatu flashover terjadi pada phasa A dan B. Semua kenaikan tegangan yang menyebabkan flashover dapat dipotong oleh arrester sehingga berada di bawah tegangan karakteristik flashover isolator yang berarti penggunaan arrester pada saluran transmisi dapat mencegah terjadinya flashover Kata Kunci : : petir, sistem transmisi, flashover, arrester, pentanahan | |
| dc.identifier.uri | https://ailib.my.id/handle/123456789/47705 | |
| dc.language.iso | id | |
| dc.publisher | Universitas Andalas | |
| dc.subject | petir | |
| dc.subject | sistem transmisi | |
| dc.subject | flashover | |
| dc.subject | arrester | |
| dc.subject | pentanahan | |
| dc.subject.classification | TK Electrical engineering. Electronics Nuclear engineering | |
| dc.title | ANALISA KINERJA ARRESTER TERHADAP FLASHOVER PADA SALURAN TRANSMISI 150 KV DI PT. PLN UPT PADANG | |
| dc.type | Thesis | |
| dcterms.dateSubmitted | 2021-02-24 | |
| dcterms.references | [1] D. Mestriner, M. Nicora, R. Procopio, M. Brignone, M. Rossi, F. Delfino, et al., "Lightning Current Parameters Effects on the Induced Overvoltages in Transmission Lines," in 2019 IEEE International Conference on Environment and Electrical Engineering and 2019 IEEE Industrial and Commercial Power Systems Europe (EEEIC / I&CPS Europe), 2019, pp. 1-5. [2] M. Ogiso, S. Komori, S. Yasui, T. Yamamoto, and H. Kobayashi, "Consideration of generating mechanism of the overvoltage between the ground wires in a building struck directly by lightning," Electrical Engineering in Japan, vol. 212, pp. 43-50, 2020. [3] B. Thangabalan and S. Das, "Understanding the Flashover Characteristics across Stay Arm Insulator due to Lightning Stroke," in 2019 11th AsiaPacific International Conference on Lightning (APL), 2019, pp. 1-5. [4] H. Swalehe, V. Pius, and B. Marungsri, "Flashover and Back-Flashover Analysis with Lightning Strokes of 69 kV and 24 kV Lines in Thailand Using ATP/EMTP," 2018, vol. 6, 2018. [5] C. Romualdo-Torres, M. Ramirez-Gonzaez, and A. Escamilla-Paz, "Lightning outage transmission line reliability improvement with surge arresters," in 2016 IEEE/PES Transmission and Distribution Conference and Exposition (T&D), 2016, pp. 1-5. [6] A. Font, S. İlhan, and A. Özdemir, "Line surge arrester application for a 380 kV power transmission line," in 2016 IEEE International Conference on High Voltage Engineering and Application (ICHVE), 2016, pp. 1-4. [7] N. Malcolm and R. K. Aggarwal, "An analysis of reducing back flashover faults with surge arresters on 69/138 kV double circuit transmission lines due to direct lightning strikes on the shield wires," in 12th IET International Conference on Developments in Power System Protection (DPSP 2014), 2014, pp. 1-6. [8] M. Banjanin, "Line arresters and underbuilt wire application in lightning protection of 110 kV and 220 kV overhead transmission lines," in 2019 18th International Symposium INFOTEH-JAHORINA (INFOTEH), 2019, pp. 1-5. [9] A. W. Muhamad Marin Bakhtiar, and Abdul Syakur "Perancangan External Lightning Protection Gedung Di Komplek PLTG Gorontalo 100 MW Dengan Metode Rolling Sphere, Protection Angle, Dan Collecting Volume," Departemen Teknik Elektro, Fakultas Teknik, Universitas Diponegoro vol. 1, p. 7, Juli 2017 Juli 2017. [10] Gassing, "Analisis Sistem Proteksi Petir (Lightning Perfomance) pada SUTT 150 kV Sistem Sulawesi Selatan," Hasil Penelitian Fakultas Teknik, vol. 1, 2012. [11] S. Hidayat and R. Zoro, "Observation of Lightning Discharges in Indonesia by Lightning Detection Network," in 2006 IEEE 8th International Conference on Properties & applications of Dielectric Materials, 2006, pp. 844-847. 69 [12] A. Ametani and T. Kawamura, "A method of a lightning surge analysis recommended in Japan using EMTP," IEEE Transactions on Power Delivery, vol. 20, pp. 867-875, 2005. [13] P. PLN, "Buku Kriteria Dasar Bagi Perencanaan Saluran Udara Tegangan Tinggi 66 kV dan 150 kV," Jakarta, vol. No. 055/DIR/78, 1978. [14] M. Nawir, "Pengaruh Tahanan Kaki Menara Saluran Transmisi Terhadap Distribusi Tegangan Surja Petir," Tesis, vol. Jurusan Teknik Elektro Universitas Gajah Mada, Yogyakarta, 2003. [15] Y. d. Dhimas, "Pengaruh Penambahan CuO Terhadap Karakteristik Eliktrik Pada Keramik Varistor ZnO Dengan Suhu Penyinteran 13000 C," vol. 1, 2010. [16] W. D. Niebuhr, "Application of Metal-Oxide-Varistor Surge Arresters on Distribution Systems," IEEE Transactions on Power Apparatus and Systems, vol. PAS-101, pp. 1711-1715, 1982. [17] F. Giraudet, "Various Benefts for Line Surge Arrester Application and Advantages of Externally Gapped Line Arresters," in 2019 International Conference on High Voltage Engineering and Technology (ICHVET), 2019, pp. 1-6. [18] Y. Zhao, D. Tang, S. Bai, Y. Liu, and D. Xu, "Influence of europium addition on microstructure and electrical properties of CCTO ceramics," in 2011 Symposium on Piezoelectricity, Acoustic Waves and Device Applications (SPAWDA), 2011, pp. 274-278. [19] N. Z. A. Malik, "Correlation Between Third Harmonic Leakage Current and Thermography Image of Zinc Oxide Surge Arrester for Fault Monitoring Using Artificial Neural Network," vol. 554, pp. 598-602, 2014. [20] I. W. Group, "Estimating lightning performance of transmission lines. II. Updates to analytical models," IEEE Transactions on Power Delivery, vol. 8, pp. 1254-1267, 1993. [21] P. Y. a. S. Premrudeepreechacharn, "Analysis of Tower Footing Resistance Effected Back Flashover Across Insulator in a Transmission System," International Converence on Power System Transient, vol. 1, 2007. [22] T. Klimchack, "Grounding Tutorial Substation Ground System Design & Standard IEEE 80," vol. 1, 2000. | |
| local.eprints.dir | disk0/00/07/28/32 | |
| local.eprints.division | 07B | |
| local.eprints.id | 72832 | |
| local.eprints.type | thesis/diploma | |
| local.eprints.uri | http://scholar.unand.ac.id/72832/ | |
| local.fakultas | Fakultas Teknik | |
| local.prodi | S1 Teknik Elektro | |
| local.thesis.level | Skripsi |